El interruptor automático abierto (ACB) de la serie TGW1N es adecuado para redes de distribución con una frecuencia de CA de 50 Hz, un voltaje nominal de CA 380 V a CA 690 V y una corriente nominal de 200 A a 6,300 A. Se utiliza para la distribución de energía eléctrica y para la protección de circuitos y unidades de potencia contra sobrecargas, cortocircuitos, subvoltajes, fallas de puesta a tierra monofásicas o corriente residual.
Certificaciones y Normas Internacionales:
Certificaciones: CE, CB
Cumplimiento de normas: IEC/EN60947-2

| Basic parameters | ||||||||||||
| Frame current | 1600 | 2000 | 2500 | 3200 | 4000 | 6300 | ||||||
| Rated working voltage Ue(V) | AC415/690 | AC400/690 | ||||||||||
| Rated insulation voltage Ui(V) | 1000 | |||||||||||
| Rated impulse withstand voltage Uimp(kV) | 12 | |||||||||||
| Frequency (HZ) | 50 | |||||||||||
| Use category | B | |||||||||||
| Pole number | 3P/4P | 3P | 3P/4P | |||||||||
| Maximum continuous current of N pole (A) | 100%In | / | 50%In | |||||||||
| Full-breaking delay time without addition (ms) | ≤30 | |||||||||||
| Closing time (ms) | ≤70 | |||||||||||
| Flashover distance (mm) | 0 | |||||||||||
| Rated current In(A) | 200/400/630 800/1000 1250/1600 | 200/250/400 500/630/800 1000/1250 1600/1900 2000 | 630/800 1000/1250 1600/2000 2500 | 2000/2500 2900/3150 3200 | 4000 | 4000/4900 5000/5900 6300 | ||||||
| Breaking capacity | ||||||||||||
| Breaking capacity | Conventional | H | Conventional | H | Conventional | H | Conventional | H | Conventional | H | —— | |
| Rated ultimate short-circuit breaking capacity Icu(kA) | AC400V | 50 | 55 | 80 | 90 | 100 | 100 | 100 | 100 | 100 | 100 | 120 |
| AC690V | 25 | 30 | 50 | 65 | 65 | 65 | 65 | 65 | 65 | 65 | 75 | |
| Rated operating short-circuit breaking capacity Ics(kA) | AC400V | 42 | 50 | 80 | 90 | 80 | 100 | 80 | 100 | 80 | 100 | 100 |
| AC690V | 20 | 25 | 40 | 65 | 50 | 65 | 50 | 65 | 50 | 65 | 65 | |
| Rated short-time withstand current Icw(kA)/1s | AC400V | 42 | 50 | 55 | 65 | 80 | 80 | 80 | 80 | 80 | 80 | 100 |
| AC690V | 20 | 25 | 40 | 50 | 50 | 50 | 50 | 50 | 50 | 50 | 65 | |
| Rated short-time withstand current Icw(kA)/0.5s | AC400V | / | / | / | 75 | / | 100 | / | 100 | / | 100 | / |
| AC690V | / | / | / | 65 | / | 65 | / | 65 | / | 65 | / | |